Fire stopping inspection
The building already has fire stopping. Is it any good?
- Every seal labelled and photographed
- BM TRADA / FIRAS-certificated contractors
- Written price before any work
This is for buildings that already have fire stopping in them. New builds at handover. Blocks where another firm sealed the risers a few years ago. Any building where trades have been in since.
The question is different from a survey. A survey asks where the holes are. An inspection asks whether the seals in the holes are what they should be.

What we look at on each seal
Is there a label? Does the label match a record?
Is the product one that is made for fire stopping? Builders' foam, plain silicone and squashed mineral wool all turn up. None of them is a tested seal on its own.
Does the seal fill the hole? Batts with a gap at the top. Mastic that only goes 10mm into a 100mm wall. Collars fitted to the wrong side of a slab.
Has anything been added since? A new cable pushed through an old batt leaves a slit. A plumber's new waste pipe with no collar.
Is it damaged? Seals get knocked by people working in risers.
An example from a school
The photo on this page is from a school block we worked on. A plastic conduit goes into a block wall with a ring of filler round it. There was no label on it.
It went on the list as a gap to be sealed. Filler of unknown type, with no label and no record, is treated as open. It may once have been fine, but nobody can show that it is.
The result
A list of every seal we looked at. Pass, or fail with the reason. Photos of both.
For each fail, the fix and a price, if you want it. Our BM TRADA / FIRAS-certificated contractors can carry out the repairs.
Sampling or every seal
A full inspection checks every seal we can reach. In a large building, you may want a sample first, such as two risers and one floor of corridors. If the sample is bad, the rest usually is too.
Send the page that mentions it, the postcode and the number of floors. We come back with what it needs and a written price.